Different backflow preventers have different test steps. An RP gets its relief valve checked, a double check needs both checks to hold, and a vacuum breaker gets its air inlet tested. We run the right steps for yours, then file the results. Price goes by size, not type.
- Price$105 flat
- TimeUnder an hour
- SchedulingSame week
- FilingIncluded
Devices we test
- Reduced pressure (RP or RPZ) assemblies
- Spill-resistant vacuum breakers (SVB)
- Double check valve assemblies
- Pressure vacuum breakers (PVB)
- Fire line detector assemblies (DCDA, RPDA)
Pricing
| Backflow size | Flat fee per backflow |
|---|---|
| Under 4" | $105 |
| 4" and larger | $175 |
Includes the test and filing with your water district. No hidden fees.
How we test an RP or RPZ
A reduced pressure principle assembly, often called an RP or RPZ, is the device used on high-hazard connections. It has two check valves with a relief valve between them. If either check leaks, the relief valve opens and dumps water out of the bottom instead of letting it travel backward.
Testing an RP takes a few more steps than other devices. The tester checks the point where the relief valve starts to open, then checks the first check valve and the second check valve to make sure each one holds tight.
Because RPs protect against the worst kinds of contamination, districts watch them closely. A relief valve that drips during normal use is a common sign that the first check is fouled or worn. We'll point that out even if the device squeaks by on test day, since it usually means a failure is coming.
Testing double check valve assemblies
A double check valve assembly has two independent check valves in a row and no relief valve. It's approved for lower-hazard connections, like many fire sprinkler systems and some irrigation and domestic lines.
The test confirms that each check valve holds pressure in the direction it's supposed to. The tester isolates each check in turn using the shutoff valves and test cocks, then reads the gauge.
Double checks are often installed below ground in vaults or boxes, especially on fire lines. That can make access the hardest part of the job. If your device sits in a vault that fills with water or dirt, let us know when you book so we come ready to pump it out before the test.
Testing PVBs and SVBs
Pressure vacuum breakers (PVBs) and spill-resistant vacuum breakers (SVBs) are the devices you see sticking up above ground on a lot of La Mesa sprinkler systems. They protect against backsiphonage, which happens when pressure on the street side drops and water could get pulled back out of your lines.
Each has a spring-loaded check valve and an air inlet that opens to break a vacuum. The test confirms the air inlet opens when it should and the check valve holds.
These devices have to sit higher than every sprinkler head or outlet downstream of them. If yours was installed too low, it may pass the test but still not meet code. We'll mention it if we see it, so you're not surprised by a district inspection later.
Testing devices on fire sprinkler services
Fire sprinkler services usually have a detector assembly, either a double check type (DCDA) or a reduced pressure type (RPDA). A small bypass line with a meter runs alongside the main device to show whether water is moving through the fire line.
Both the main assembly and the bypass get tested. Since most fire line devices are 4 inches or bigger, they fall in our $175 per device tier.
Because shutting a fire line valve can set off alarms or affect monitoring, we talk with you or your building manager before we start. If an alarm company needs to be notified, we'll let you know ahead of time so the test goes smoothly.
Figuring out which type you have
Most devices have the manufacturer's name and model cast into the body or printed on a tag. The model number usually tells you the type. If you can't read it, shape helps: an RP has a relief valve port on the bottom between two checks, a double check has two check covers and no relief port, and a PVB or SVB has a bonnet on top with a single check.
You don't need to know before you book. A photo is enough for us to tell, and the tester confirms it on site before starting.
How age affects results
Device type matters less than condition when it comes to passing. A ten-year-old double check that has been rebuilt on schedule can pass easily, while a three-year-old RP on a line full of debris can fail.
That said, older devices do fail more often as rubber ages and parts wear. If yours is old enough that parts are getting hard to find, we'll mention it, so replacement can be planned instead of rushed.
Don't know which one you have?
See how to tell RP, double check and PVB apart, or just send us a photo.
Questions
Which type is most common on homes?
On sprinkler lines it's usually a PVB or double check. On the main line it's often a double check or RP.
Do fire line devices need the fire department?
Usually not for the test itself, but we coordinate with you first since closing valves can trigger alarms.
Is the price different for an RP?
No. We charge by size: $105 under 4 inches, $175 for 4 inches and larger.
Can you test a device installed underground?
Yes. Let us know when you book if the vault fills with water or dirt so we come ready to clear it.
Is an RPZ the same as an RP?
Yes. Both names refer to a reduced pressure principle assembly.
Do all types cost the same to test?
Pricing goes by size, not type: $105 for devices under 4 inches and $175 for 4 inches and up.
Serving La Mesa and the towns next door
We handle backflow preventer testing in La Mesa, Lemon Grove, Spring Valley, College Area, Casa de Oro-Mount Helix and El Cajon. Most visits are booked within the week.
Why people around La Mesa call us
We're a local company and backflow prevention is our focus. Every test is done by a certified tester with a calibrated gauge, and filing with your water district is part of the price, not an extra.
You'll know the cost before we start: $105 for devices under 4 inches, $175 for 4 inches and up, and free quotes for everything else. The office answers seven days a week, 6am to midnight, and emergency calls are taken around the clock.
Most of our customers are homeowners with one device on the sprinkler line, but we also test for landlords, HOAs, churches, schools and shops around La Mesa. Whoever you are, the visit works the same way: we call ahead, test the device, explain anything that came up, and send the report to the district before the day is out. If something needs fixing, you decide whether and when.